Conduit Fill Calculator

NEC Table 310.16 · 310.15(B)(1) · 310.15(C)(1)

Ampacity Calculator

See the allowable ampacity of any wire size after correcting for ambient temperature and adjusting for the number of current-carrying conductors in the raceway.

Adjusted ampacity
–
Table value
–
Ambient
–
Bundling
–

How to use the ampacity calculator

  1. Select the wire size and material.
  2. Pick the temperature rating of the insulation (60°C, 75°C or 90°C).
  3. Enter the ambient temperature where the wire runs — attics and rooftops are often far above 30°C.
  4. Enter how many current-carrying conductors share the raceway or cable.

Ampacity derating formula

Adjusted ampacity = Table 310.16 ampacity × temperature correction factor × adjustment factor

Worked example

Six 8 AWG copper THWN-2 conductors (90°C) in a conduit through a 40°C space. Start at 55 A (90°C column). The temperature factor for 36–40°C is 0.91, and six conductors get 80%: 55 × 0.91 × 0.80 = 40.0 A. Because the terminals are 75°C, also check the 75°C value (50 A); the lower number, 40 A, governs.

Ambient temperature correction (Table 310.15(B)(1))

Ambient °CAmbient °F60°C75°C90°C
10 or less50 or less1.291.21.15
11–1552–591.221.151.12
16–2061–681.151.111.08
21–2570–771.081.051.04
26–3079–86111
31–3588–950.910.940.96
36–4097–1040.820.880.91
41–45106–1130.710.820.87
46–50115–1220.580.750.82
51–55124–1310.410.670.76
56–60133–140—0.580.71
61–65142–149—0.470.65
66–70151–158—0.330.58
71–75160–167——0.5
76–80169–176——0.41
81–85178–185——0.29

Adjustment for more than three conductors (Table 310.15(C)(1))

Current-carrying conductorsPercent of table value
4–680%
7–970%
10–2050%
21–3045%
31–4040%
41 and above35%

Related calculations

Packing more conductors into one raceway triggers derating, so check the physical fit with the conduit fill calculator. To go straight from a load to a wire size, use the wire size calculator.

Frequently asked questions

What is ampacity?

Ampacity is the maximum current, in amperes, a conductor can carry continuously under its conditions of use without exceeding its temperature rating (NEC Article 100).

What is the ampacity of 12 AWG copper?

Table 310.16 lists 20 A at 60°C, 25 A at 75°C and 30 A at 90°C. But 240.4(D) limits the overcurrent protection for 12 AWG copper to 20 A, so it is normally used on 20 A circuits.

When do I need to derate conductors?

When the ambient temperature is above 30°C (86°F), apply Table 310.15(B)(1). When more than three current-carrying conductors share a raceway or cable for more than 24 inches, apply Table 310.15(C)(1). If both apply, multiply both factors.

Does the neutral count as a current-carrying conductor?

A neutral that carries only the unbalanced current of a 3-wire single-phase or 4-wire three-phase wye circuit is not counted. In a 4-wire wye circuit feeding mostly nonlinear loads (computers, LED drivers), the neutral is counted (310.15(E)). Grounding conductors never count.

Can I use 90°C ampacity for derating?

Yes. For 90°C insulation such as THHN, you may start derating from the 90°C column, but the result may not exceed the ampacity of the terminal temperature rating, usually 60°C or 75°C (110.14(C)).

What is the 75°C rule?

Equipment rated over 100 A, and conductors larger than 1 AWG, generally terminate at 75°C. Circuits of 100 A or less, or 14–1 AWG conductors, must use the 60°C column unless the equipment is listed for 75°C — most modern breakers are.

More electrical calculators

Last reviewed 2026-11-15. Values from NFPA 70 (NEC) 2017–2023. For estimating only — confirm with the code edition adopted by your authority having jurisdiction.