How the wire size calculator works
- Design current. Your load in amps, multiplied by 1.25 if it runs for three hours or more.
- Base ampacity. The calculator walks up NEC Table 310.16 in the column you choose (60°C, 75°C or 90°C) for copper or aluminum.
- Correction and adjustment. Each candidate is multiplied by the ambient temperature factor from Table 310.15(B)(1) and the bundling factor from Table 310.15(C)(1).
- Small-conductor limits. 14, 12 and 10 AWG are capped at the overcurrent limits of 240.4(D) — 15, 20 and 30 A for copper.
- Voltage drop (optional). If you enter a length, the result is upsized until the drop is within your target.
Wire sizing formula
Adjusted ampacity = Table 310.16 value × ambient factor × bundling factor
Choose the smallest size where adjusted ampacity ≥ required ampacity
Worked example
A 40 A non-continuous load on copper THWN conductors with 75°C terminals, three conductors in a conduit, 30°C ambient. Table 310.16 gives 8 AWG copper 50 A at 75°C, and no correction applies, so 8 AWG is the answer. Put the same circuit in a 40°C attic with six current-carrying conductors and the 8 AWG drops to 50 × 0.88 × 0.80 = 35.2 A — too small, so the calculator moves up to 6 AWG (65 × 0.88 × 0.80 = 45.8 A).
Wire ampacity chart (NEC Table 310.16)
Allowable ampacity with no more than three current-carrying conductors at 30°C (86°F).
| Size | Cu 60°C | Cu 75°C | Cu 90°C | Al 60°C | Al 75°C | Al 90°C |
|---|---|---|---|---|---|---|
| 14 AWG | 15 | 20 | 25 | — | — | — |
| 12 AWG | 20 | 25 | 30 | 15 | 20 | 25 |
| 10 AWG | 30 | 35 | 40 | 25 | 30 | 35 |
| 8 AWG | 40 | 50 | 55 | 35 | 40 | 45 |
| 6 AWG | 55 | 65 | 75 | 40 | 50 | 55 |
| 4 AWG | 70 | 85 | 95 | 55 | 65 | 75 |
| 3 AWG | 85 | 100 | 115 | 65 | 75 | 85 |
| 2 AWG | 95 | 115 | 130 | 75 | 90 | 100 |
| 1 AWG | 110 | 130 | 145 | 85 | 100 | 115 |
| 1/0 AWG | 125 | 150 | 170 | 100 | 120 | 135 |
| 2/0 AWG | 145 | 175 | 195 | 115 | 135 | 150 |
| 3/0 AWG | 165 | 200 | 225 | 130 | 155 | 175 |
| 4/0 AWG | 195 | 230 | 260 | 150 | 180 | 205 |
| 250 kcmil | 215 | 255 | 290 | 170 | 205 | 230 |
| 300 kcmil | 240 | 285 | 320 | 195 | 230 | 260 |
| 350 kcmil | 260 | 310 | 350 | 210 | 250 | 280 |
| 400 kcmil | 280 | 335 | 380 | 225 | 270 | 305 |
| 500 kcmil | 320 | 380 | 430 | 260 | 310 | 350 |
14–10 AWG are further limited by 240.4(D): copper 15/20/30 A and aluminum 15 A (12 AWG) and 25 A (10 AWG).
Copper vs aluminum
Aluminum conducts about 61% as well as copper, so it needs to be roughly two sizes larger for the same current. It is lighter and cheaper on big feeders, but terminations must be listed for aluminum (marked AL/CU) and torqued correctly.
After you size the wire
Check how many of those conductors fit in your raceway with the conduit fill calculator, confirm the drop on long runs with the voltage drop calculator, and see the full derating breakdown in the ampacity calculator.