NEC Table 310.16 · 310.15 · 240.4(D)

Wire Size Calculator

Enter the load current and installation conditions to get the smallest copper or aluminum conductor that meets NEC ampacity rules — with an optional voltage drop check for long runs.

Voltage drop check (optional)
Recommended wire size
–
Design current
–
By ampacity
–
Adjusted ampacity
–
By voltage drop
–

NEC Table 310.16, 310.15(B)(1) & (C)(1), 240.4(D); voltage drop from Chapter 9 Table 8 resistance at 75°C.

How the wire size calculator works

  1. Design current. Your load in amps, multiplied by 1.25 if it runs for three hours or more.
  2. Base ampacity. The calculator walks up NEC Table 310.16 in the column you choose (60°C, 75°C or 90°C) for copper or aluminum.
  3. Correction and adjustment. Each candidate is multiplied by the ambient temperature factor from Table 310.15(B)(1) and the bundling factor from Table 310.15(C)(1).
  4. Small-conductor limits. 14, 12 and 10 AWG are capped at the overcurrent limits of 240.4(D) — 15, 20 and 30 A for copper.
  5. Voltage drop (optional). If you enter a length, the result is upsized until the drop is within your target.

Wire sizing formula

Required ampacity = Load × (1.25 if continuous)
Adjusted ampacity = Table 310.16 value × ambient factor × bundling factor
Choose the smallest size where adjusted ampacity ≥ required ampacity

Worked example

A 40 A non-continuous load on copper THWN conductors with 75°C terminals, three conductors in a conduit, 30°C ambient. Table 310.16 gives 8 AWG copper 50 A at 75°C, and no correction applies, so 8 AWG is the answer. Put the same circuit in a 40°C attic with six current-carrying conductors and the 8 AWG drops to 50 × 0.88 × 0.80 = 35.2 A — too small, so the calculator moves up to 6 AWG (65 × 0.88 × 0.80 = 45.8 A).

Wire ampacity chart (NEC Table 310.16)

Allowable ampacity with no more than three current-carrying conductors at 30°C (86°F).

SizeCu 60°CCu 75°CCu 90°CAl 60°CAl 75°CAl 90°C
14 AWG152025———
12 AWG202530152025
10 AWG303540253035
8 AWG405055354045
6 AWG556575405055
4 AWG708595556575
3 AWG85100115657585
2 AWG951151307590100
1 AWG11013014585100115
1/0 AWG125150170100120135
2/0 AWG145175195115135150
3/0 AWG165200225130155175
4/0 AWG195230260150180205
250 kcmil215255290170205230
300 kcmil240285320195230260
350 kcmil260310350210250280
400 kcmil280335380225270305
500 kcmil320380430260310350

14–10 AWG are further limited by 240.4(D): copper 15/20/30 A and aluminum 15 A (12 AWG) and 25 A (10 AWG).

Copper vs aluminum

Aluminum conducts about 61% as well as copper, so it needs to be roughly two sizes larger for the same current. It is lighter and cheaper on big feeders, but terminations must be listed for aluminum (marked AL/CU) and torqued correctly.

After you size the wire

Check how many of those conductors fit in your raceway with the conduit fill calculator, confirm the drop on long runs with the voltage drop calculator, and see the full derating breakdown in the ampacity calculator.

Frequently asked questions

What size wire do I need for 30 amps?

For copper in the 60°C or 75°C column, 10 AWG is rated 30 A or 35 A and is the usual choice for a 30 A circuit. With aluminum you need 8 AWG. Long runs may need a bigger size for voltage drop.

What size wire for a 50 amp circuit?

Copper 8 AWG is rated 50 A at 75°C, so it works where both ends are rated 75°C. If the equipment terminals are only rated 60°C, use 6 AWG copper (55 A). Aluminum needs 6 AWG at 75°C (50 A).

What size wire for 100 amps?

At 75°C, 3 AWG copper (100 A) or 1 AWG aluminum (100 A). For a dwelling service or main feeder, NEC 310.12 allows a smaller size (83% rule), which this calculator does not apply.

Why does the calculator use 125% for continuous loads?

NEC 210.19(A) and 215.2(A) require conductors for continuous loads (three hours or more) to be sized at 125% of that load. A 16 A continuous load therefore needs a conductor good for 20 A.

Should I use the 90°C column for THHN?

You can use the 90°C ampacity as the starting point for derating, but the final ampacity is usually limited by the 60°C or 75°C rating of the breaker and equipment terminals (110.14(C)).

Does wire size depend on distance?

Ampacity does not, but voltage drop does. On long runs, a wire that is large enough for the current can still lose too much voltage. Enter the one-way length to have the calculator upsize for a 3% limit.

More electrical calculators

Last reviewed 2026-11-15. Values from NFPA 70 (NEC) 2017–2023. For estimating only — confirm with the code edition adopted by your authority having jurisdiction.