Find how many volts a circuit loses over distance, what voltage reaches the load and which wire size keeps the drop under your target.

Voltage drop
–
Voltage at load
–
Resistance
–

Uses NEC Chapter 9 Table 8 DC resistance at 75°C (uncoated copper, stranded). AC results for large conductors can differ slightly because of reactance (Table 9).

How to use the voltage drop calculator

  1. Pick single-phase/DC or three-phase and enter the source voltage.
  2. Enter the load current and the one-way length from the panel to the load.
  3. Choose copper or aluminum and the wire size. Use parallel sets for large feeders.
  4. Read the drop in volts and percent. If it's over your target, the calculator suggests the smallest size that passes.

Voltage drop formula

Single-phase / DC: VD = 2 × I × R × L ÷ 1000
Three-phase: VD = 1.732 × I × R × L ÷ 1000
VD % = VD ÷ source voltage × 100

R is the conductor resistance in ohms per 1,000 feet from NEC Chapter 9, Table 8 (for example 1.98 Ω for 12 AWG stranded copper at 75°C). L is the one-way length in feet.

Worked example

A 20 A load, 100 feet from the panel, on 12 AWG copper at 120 V single-phase: VD = 2 × 20 × 1.98 × 100 ÷ 1000 = 7.92 V, or 6.6%. That's more than double the 3% guideline, so the calculator recommends upsizing. With 8 AWG (0.778 Ω) the drop falls to 3.11 V — 2.6%.

Voltage drop table: copper, 120 V single-phase, 20 A

WireΩ/1000 ft50 ft100 ft150 ft200 ft
14 AWG3.145.2%10.5%15.7%20.9%
12 AWG1.983.3%6.6%9.9%13.2%
10 AWG1.242.1%4.1%6.2%8.3%
8 AWG0.7781.3%2.6%3.9%5.2%
6 AWG0.4910.8%1.6%2.5%3.3%
4 AWG0.3080.5%1.0%1.5%2.1%
3 AWG0.2450.4%0.8%1.2%1.6%
2 AWG0.1940.3%0.6%1.0%1.3%
1 AWG0.1540.3%0.5%0.8%1.0%
1/0 AWG0.1220.2%0.4%0.6%0.8%
2/0 AWG0.09670.2%0.3%0.5%0.6%
3/0 AWG0.07660.1%0.3%0.4%0.5%
4/0 AWG0.06080.1%0.2%0.3%0.4%
250 kcmil0.05150.1%0.2%0.3%0.3%
350 kcmil0.03670.1%0.1%0.2%0.2%
500 kcmil0.02580.0%0.1%0.1%0.2%

Conductor resistance (NEC Table 8, 75°C)

SizeCircular milsCopper Ω/kftAluminum Ω/kft
14 AWG4,1103.145.17
12 AWG6,5301.983.25
10 AWG10,3801.242.04
8 AWG16,5100.7781.28
6 AWG26,2400.4910.808
4 AWG41,7400.3080.508
3 AWG52,6200.2450.403
2 AWG66,3600.1940.319
1 AWG83,6900.1540.253
1/0 AWG105,6000.1220.201
2/0 AWG133,1000.09670.159
3/0 AWG167,8000.07660.126
4/0 AWG211,6000.06080.1
250 kcmil250,0000.05150.0847
350 kcmil350,0000.03670.0605
500 kcmil500,0000.02580.0424

Ways to reduce voltage drop

  • Use a larger conductor — each three-AWG step roughly halves resistance.
  • Raise the voltage: the same load at 240 V draws half the current and loses a quarter of the percentage.
  • Shorten the route or move the panel closer to the load.
  • Run conductors in parallel for big feeders (1/0 and larger, NEC 310.10(G)).

Bigger wire takes more room, so re-check your raceway with the conduit fill calculator and confirm ampacity with the wire size calculator.

Frequently asked questions

What is an acceptable voltage drop?

The NEC does not make voltage drop mandatory for ordinary circuits, but Informational Notes to 210.19 and 215.2 recommend no more than 3% on a branch circuit or feeder and 5% total from the service to the farthest outlet.

How do you calculate voltage drop?

For single-phase or DC circuits: VD = 2 × I × R × L ÷ 1000. For three-phase: VD = 1.732 × I × R × L ÷ 1000. I is current in amps, L is one-way length in feet and R is resistance in ohms per 1,000 ft from NEC Chapter 9 Table 8.

Why is the length multiplied by 2 for single-phase?

Current flows out on one conductor and back on the other, so the total wire length is twice the one-way distance. In a balanced three-phase circuit the factor is √3 (1.732) instead.

How far can you run 12 gauge wire on 20 amps?

At 120 V with copper and a 3% limit (3.6 V), 12 AWG reaches about 45 feet one way at a full 20 A. At 240 V the distance doubles to roughly 90 feet. At lighter loads you can go further.

Does aluminum wire have more voltage drop?

Yes. Aluminum has about 1.6 times the resistance of copper of the same size, so you typically go up two sizes in aluminum to get the same voltage drop.

Is this calculator accurate for AC?

It uses DC resistance at 75°C from Table 8, which is the standard approximation and very close for sizes up to about 1/0. For large AC feeders, reactance (Table 9) adds a little extra drop at lower power factors.