How to use the box fill calculator
- Count the conductors by size that enter the box (hots, neutrals, travelers). A wire that passes through unbroken counts once.
- Tick internal cable clamps if the box has them.
- Add device yokes (each switch or receptacle strap) and the largest wire connected to them.
- Enter the number of equipment grounding conductors.
- Pick a standard box or type the volume marked inside the box.
Box fill formula (NEC 314.16(B))
| Conductor size | Volume allowance |
|---|---|
| 6 AWG | 5.00 in³ |
| 8 AWG | 3.00 in³ |
| 10 AWG | 2.50 in³ |
| 12 AWG | 2.25 in³ |
| 14 AWG | 2.00 in³ |
| 16 AWG | 1.75 in³ |
| 18 AWG | 1.50 in³ |
Worked example
A receptacle fed through with two 12/2 NM cables: four 12 AWG conductors (4 × 2.25 = 9.00 in³), internal clamps (2.25), one device yoke (2 × 2.25 = 4.50) and two grounds counted once (2.25). Total: 18.0 in³. A 3 × 2 × 3-1/2 device box (18.0 in³) just makes it; a 4 × 1-1/2 square box (21.0 in³) gives some breathing room.
Standard metal box volumes (Table 314.16(A))
| Box (trade size) | Volume | Max 14 AWG | Max 12 AWG |
|---|---|---|---|
| 4 × 1-1/4 round/octagonal | 12.5 in³ | 6 | 5 |
| 4 × 1-1/2 round/octagonal | 15.5 in³ | 7 | 6 |
| 4 × 2-1/8 round/octagonal | 21.5 in³ | 10 | 9 |
| 4 × 1-1/4 square | 18.0 in³ | 9 | 8 |
| 4 × 1-1/2 square | 21.0 in³ | 10 | 9 |
| 4 × 2-1/8 square | 30.3 in³ | 15 | 13 |
| 4-11/16 × 1-1/4 square | 25.5 in³ | 12 | 11 |
| 4-11/16 × 1-1/2 square | 29.5 in³ | 14 | 13 |
| 4-11/16 × 2-1/8 square | 42.0 in³ | 21 | 18 |
| 3 × 2 × 1-1/2 device | 7.5 in³ | 3 | 3 |
| 3 × 2 × 2 device | 10.0 in³ | 5 | 4 |
| 3 × 2 × 2-1/4 device | 10.5 in³ | 5 | 4 |
| 3 × 2 × 2-1/2 device | 12.5 in³ | 6 | 5 |
| 3 × 2 × 2-3/4 device | 14.0 in³ | 7 | 6 |
| 3 × 2 × 3-1/2 device | 18.0 in³ | 9 | 8 |
| 4 × 2-1/8 × 1-1/2 device | 10.3 in³ | 5 | 4 |
| 4 × 2-1/8 × 1-7/8 device | 13.0 in³ | 6 | 5 |
| 4 × 2-1/8 × 2-1/8 device | 14.5 in³ | 7 | 6 |
| 3-3/4 × 2 × 2-1/2 masonry box/gang | 14.0 in³ | 7 | 6 |
| 3-3/4 × 2 × 3-1/2 masonry box/gang | 21.0 in³ | 10 | 9 |
Max conductor counts assume no clamps, devices or grounds.
Box fill vs conduit fill
Boxes are sized by volume under 314.16; raceways are sized by cross-sectional area under Chapter 9. If you're planning the conduit between boxes, use the conduit fill calculator.